Troubleshooting
Diagnostic Procedure for Check Code
Check code Operation cause
1. Indoor unit in automatic addressing mode
[dE] 2. Indoor unit P.C. board setup error
Indoor address undefined 3. Defective indoor unit P.C. board
4. Communication noise interference
While this check code is displayed, wait for a moment. When the address is defined, the
operation is automatically reset. However, if the check code does not disappear
20 minutes after the power source was turned on, a fault is considered. Check the following
items.
Fault check of indoor unit P.C. board
Source check of communication noise interference
Incorrect setup of jumper options on indoor unit P.C. board
Check code Operation cause
1. Outdoor unit in automatic addressing mode
[dF]
2. Defective indoor unit interface P.C. board
Outdoor address undefined
3. Communication noise interference
While this check code is displayed, wait for a moment. When the address is defined, the
operation is automatically reset. However, if the check code does not disappear 20 minutes
after the power source was turned on, a fault is considered. Check the
following items.
Fault check of outdoor unit interface P.C. board
Source check of communication noise interference between outdoor units