Troubleshooting
Diagnostic Procedure for Check Code
Check code Operation cause
1. Indoor unit in automatic addressing mode
[dE] 2. Indoor unit P.C. board setup error
Indoor address undefined 3. Defective indoor unit P.C. board
4. Communication noise interference
While this check code is displayed, wait for a moment. When the address is defined, the
operation is automatically reset. However, if the check code does not disappear
20 minutes after the power source was turned on, a fault is considered. Check the following
items.
• Fault check of indoor unit P.C. board
• Source check of communication noise interference
• Incorrect setup of jumper options on indoor unit P.C. board
Check code Operation cause
1. Outdoor unit in automatic addressing mode
[dF]
2. Defective indoor unit interface P.C. board
Outdoor address undefined
3. Communication noise interference
While this check code is displayed, wait for a moment. When the address is defined, the
operation is automatically reset. However, if the check code does not disappear 20 minutes
after the power source was turned on, a fault is considered. Check the
following items.
• Fault check of outdoor unit interface P.C. board
• Source check of communication noise interference between outdoor units