Diagnostic Procedure for Check Code
86
14
Check code Operation cause
1. Outdoor unit service valve closed
2. Cooling bypass PMV error
[AE] 3. TD1 sensor error
TD1 condition gas leak detection 4. Insufficient refrigerant, blockage in pipe
5. Blockage of indoor filter
6. Blockage of PMV assembly on the liquid line
Are the gas pipe and liquid
pipe service valves of the
outdoor unit fully open?
Is there a blockage
in the PMV assembly on
the liquid line?
Open valves fully.
Replace TD1 sensor.
Replace both the PMVs.
No
Yes
Yes
No
Are the resistance characteristics
of TD1 sensor normal?
No
Yes
Insufficient refrigerant,
blockage, pipe breakage.
(Check miswiring of the outdoor unit according to miswiring check function.)
Check code Operation cause
[AF] Abnormal power phase order or missing phase of
Phase order alarm power supply to the outdoor unit
There is an abnormal power phase order or missing phase of power supply to the outdoor
unit. Check power supply wiring.
Set normal wiring.
Is the wiring correct?
No
Yes
Cooling bypass PMV B error
Is the cooling bypass
PMV B normal?
No
Yes