Service manual

Troubleshooting
Diagnostic Procedure for Check Code
84
14
Check code Operation cause
1. Outdoor unit service valve closed
[A7] 2. Blockage PMV assembly on the liquid line
TS condition gas leak detection 3. TS sensor error
4. Insufficient refrigerant, blockage in pipe
Are the gas pipe and liquid
pipe service valves of the
outdoor unit fully open?
Is there a blockage
in the PMV assembly on the
liquid line?
Open valves fully.
Replace TS sensor.
Replace both the PMVs.
No
Yes
Yes
No
Are the resistance characteristics
of TS sensor normal?
No
Yes
Insufficient refrigerant,
blockage, pipe breakage.
Check code Operation cause
[AA]
Pd sensor output voltage alarm
Pd sensor alarm
If there is an abnormal output voltage of Pd sensor: Check connector circuit
(Pd sensor: CN501) and output voltage of the sensor.
If the sensor is normal, replace the outdoor interface P.C. board.