Service manual

66
14
Troubleshooting
Diagnostic Procedure for Check Code
Check code Operation cause
1. Irregularity of power source
[12]
2. Noise of peripheral equipment
Other indoor alarm
3. Defective indoor P.C. board
Check code Operation cause
1. Fan motor circuit connection error
[11] 2. Capacitor error
Indoor fan motor alarm 3. Fan motor error
4. Defective indoor P.C. board
Does indoor fan operate
for a short period after
resetting and resuming?
Is there a connection
error of CN18 connector?
Is there an irregularity
of power source?
Is there a connection
error of CN07 connector?
Is capacitor normal?
Confirm there is no mechanical
lock on the fan motor?
Is approx. DC12V to
13V output to CN18
connector 1-3 pins?
Is revolution pulse
input from hole IC to
CN18 connector 2-3 pins
during fan operation?
(Measurement by tester:
Approx. DC2 to 2.5V)
Modify connection and wiring.
Replace capacitor.
Replace fan motor.
Replace MCC-1355-01
P.C. board
Check power source voltage,
modify lines, remove noise, etc.
Indoor P.C. board check
Defective Replacement
No
Yes
No
No
No
Yes
Yes
Yes
Yes
No
No
Yes
No
Yes
Yes
No