Service manual
52
12
Self Diagnostic Display Information
Outdoor Units
SW03 SW02 SW01 Displayed content
3 1 1 Use refrigerant Type of refrigerant used is displayed. AB
• In case of R22 model 22
• In case of R407C model 40 7C
2 Outdoor system A 8] to [46]: 8 to 46HP
capacity
B [HP]
3 No. of connected A [1] to [ 5]: 1 to 5 units
outdoor units
B[ P ]
4 No. of connected A [0] to [40]: 0 to 40 units
indoor units
B[ P ]
5 No. of operating A [0] to [40]: 0 to 40 units
indoor units
B[ P ]
6—A
—
B
7 Release control A [r ]: Normal operation, [r1]: Under release control
operation
B—
8 Oil equalizing pattern A [OL]
B [P ]: Normal operation, [P1] to [P3]: Oil equalizing patterns 1 to 3A
9—A —
B—
10 Refrigerant/Oil A [C-]: Normal operation, [C1]: Under cooling oil recovery control
recovery operation
B [H-]: Normal operation, [H1]: Under heating refrigerant recovery
11 Automatic address A [Ad]
B [ ]: In normal time (Automatic address setup completes)
[11]: Under automatic address setup
12 — —
13 — —
14 — —
15 — —
16 — —
System information data display (Displayed on the inverter unit only)
SW01, 02, 03: Rotary switch
SW04, 05: Push switch
SW08: Dip switch
The combination of rotary switches SW01,
SW02 and SW03 display the following info: