Service manual

17
6
Construction Views
Indoor Units
17
Built-In Duct
MM-B056, MM-B080, MM-B112, MM-B140
200
450
450
300-400
Inspection
hole
Provide an inspection
hole in this position
Ensure that there is sufficient space around the
indoor unit for installation and servicing
Indoor unit
Model A B E ØF ØG H J K M N
MM-B056 700 750 780 12.7 6.4 252 280 280 1 2
MM-
B080 1,000 1,050 1,080 15.9 9.5 252 580 290 2 3
MM-B112, B140 1,350 1,400 1,430 19.0 9.5 252 930 310 3 4
(Gas ØF)
Hanging Bolt Pitch B
Refrigerant Pipe
Connection
Unit Dimension A
Hanging Bolt
4-M10
Provided at site
Nx Ø200
Air Outlet
Drain pipe connection
(inner diameter 32)
(diameter 32 minimal for PVC pipes)
Refrigerant pipe
connection (Liquid ØG)
Hanging Bolt Pitch:565
Unit Dimension:800
J = M x K
(H)
6 x Ø4 holes (Ø160)
Fresh air inlet Ø125
cut-out (other side)
Filter kit
(Unit: mm)