Installation guide

Web Server Installation Guide Page 10
CDU-AC5
5.1 General
A CDU-AC5 can monitor and control a number of CDUs. The number of CDUs which can be
connected to the CDU-AC5 is dependent on the CDU-AC5 firmware. As of writing the
following firmware images are available,
CDU-AC5 Firmware Version
Maximum number of CDUs
3CDU 1.0.0 onwards
3
8CDU 1.0.0 onwards
8
A CDU must be connected to the CDU-AC5 gateway using the procedure documented in this
section.
5.2 Configuring the CDU’s Network Address
Before a CDU can be attached to the CDU-AC5 gateway it must be given a unique network
address. Typically, network addresses are allocated to CDUs in ascending order, starting
from 1. Configuration of the CDU network address is carried out via the CDU’s graphical
display.
i. Logon at Service Level or above.
ii. Navigate to `Connectivity->N/W Address (screen level 8-1)
iii. Press OK
iv. Enter the required network address
v. Press OK
5.3 Attaching the CDU to the CDU-AC5
i. Logon at Service Level or above.
ii. Navigate to Connectivity->Web Server->Attach (screen level 8-2-1)
iii. Press OK. The screen shown below will be displayed.
iv. Press the Service button of the CDU-AC5.
v. The screen will report the status of the attachment process. A series of screen
updates will be displayed.
CONFIGURATION
Section 5
N/W Address
Use Arrow keys
01
Attach
Press serv. pin