5.0 MAINTENANCE AND STORAGE
!
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect the power supply before performing any service or
maintenance. Failure to do so may result in serious injury or death.
5.1 REMOVING THE COOLING MEDIA
In order to perform any maintenance on internal components, the cooling
pads must be removed to access the inside of the unit.
1. Pop pad grilles from support channel.
2. Tilt pads from the top; lift out of the unit.
5.2 DAILY MAINTENANCE
Turn off the pump approximately 15 minutes before the fan is turned off at
the end of each use. This allows the pads to drain and dry out - controling
mildew and bacteria growth and ensuring long and efficient pad life.
Drain water in the unit if it will be unused for a prolonged period of time.
5.3 PERIODIC MAINTENANCE
The cooling media (pads) acts as a filtering agent and removes dust and
other particles from the incoming air stream. These particles will flow into
the sump and collect there. Water impurities will also collect in the sump
(water treatment tablets available at cool-space.com). In order to keep the
FLURRY operating at peak efficiency you will need to keep the cooling
media and the sump clear of debris.
DRAINING THE WATER SUMP
1. Turn unit off and disconnect the power supply
2. Remove drain plug located at bottom of reservoir; let unit drain
3. Remove cooling pads (refer to section 5.1)
4. Clean out reservoir with either a towel or wet/dry vacuum
5. Reinstall pads and grille
NOTE: Depending on how often you operate the unit, this procedure
should be performed anywhere from every week for heavy use to monthly
for light use.