Full Product Manual
Page 13
6.0 TROUBLESHOOTING/REPAIR
6.4 PUMP REPAIR PROCEDURES
!
CAUTION
Repairs should be performed by a qualified technician!
!
WARNING
ELECTRICAL SHOCK HAZARD
Disconnect the power supply before performing any service or
maintenance. Failure to do so may result in serious injury or death.
PUMP REPLACEMENT FOR CS6210 & CS6210HV
1. Remove cooling pads (see section 5.1 for pad removal instructions)
2. Remove switch plate and disconnect pump wire (refer to wiring
diagram on page 14).
3. Remove hose and level switch from pump.
4. Remove pump from water sump and install new pump.
5. Reverse the above procedures to reconnect the wiring, lift pump
bracket and reconnect the hose. Secure wires to fan frame with wire
ties to clear the fan blades. Be sure to position the plug correctly.
6. Reinstall cooling pads and guards, reconnect power and test pump.