Fault Procedure
• Disconnect the incoming supply (L1, L2, L3 and
control voltage) from the starter.
• Disconnect the motor cables (T1, T2,T3) from the
starter.
• Ensure the firing looms remain plugged in during
the tests.
• Using a 500 VDC insulation tester (low voltage
ohm meters or multi-meters are not adequate),
measure the resistance between the input and
output on each phase (L1-T1, L2-T2, L3-T3). The
resistance should be close to 33k
Ω.
• If the resistance measured across the SCR
measures below about 10k
Ω the SCR should be
replaced.
• If the resistance measured across the SCR is
greater than 33k
Ω there could be a control PCB
or firing loom fault.
CONTROL INPUT TEST;
This procedure verifies the integrity of circuits
connected to any of the remote control inputs. Start,
Stop, Reset and Par. Set.
• Using a volt meter measure across each input. If
24VDC is measured when the circuit is closed, the
switch/control is connected incorrectly or is faulty.