Specifications

MCD3000 Series
MG.15.A4.22 - VLT is a registered Danfoss trademark 39
Desi
g
n Guide
3. Refer to the Current Ratings tables in the
Specifications section of this manual. Select a
Start Current column within the Current Ratings
table that is greater than the required start current
calculated above. Use this column to select a
MCD3000 model with a FLC rating greater or
equal to the motor nameplate FLC.
Typical applications
MCD3000 soft starters can offer benefits for almost all
motor starting applications. Typical advantages are
highlighted in the table below.
ication Benefits
Pumps
Minimised hydraulic shock in
pipelines during start and stop.
Reduced starting current.
Minimised mechanical stress on
motor shaft.
Undercurrent protection prevents
damage from block pipe or low
water situations.
Automatic reset functionality
ensures continued operation of
unmanned pump stations.
Phase rotation protection prevents
damage from reverse pump
rotation.
Instantaneous overload protection
prevents damage from debris
sucked into the pump.
Conveyor
Belts
Controlled soft start without
mechanical shocks, e.g. bottles on
a belt do not fall over during
starting, minimised belt stretch,
reduced counter balance stress.
Controlled stop without mechanical
shocks. Soft stop.
Optimum soft start performance
even with varying starting loads,
e.g. coal conveyors started loaded
or unloaded.
Extended mechanical lifetime.
Maintenance-free.
Centrifuges
Smooth application of torque
prevents mechanical stress.
Reduced starting times over
star/delta starting.
Reduced stopping times.
(D.C.Brake and soft braking).
ation Benefits
Ski Lifts
Jerk free acceleration increases
skier comfort and prevents
swinging T-bars etc.
Reduced starting current allows
starting of large motors on a weak
power supply.
Smooth and gradual acceleration
whether the ski lift is lightly or
heavily loaded.
Phase rotation protection prevents
operation in reverse direction.
Compressors
Reduced mechanical shock
extends the life of the compressor,
couplings and motor.
Limited start current enables large
compressors to be started when
maximum power capacity is
limited.
Phase rotation protection prevents
operation in reverse direction.
Instantaneous overload protection
prevents damage possible if liquid
ammonia enters the compressor
screw.
Fans
Extended coupling life through
reduced mechanical shock.
Reduced start current enables
large fans to be started when
maximum power capacity is
limited.
Phase rotation protection prevents
operation in reverse direction.
Mixers
Gentle rotation during start-up
reduces mechanical stress.
The starting current is reduced.
Bandsaws
Reduced saw band replacement
times because the MCD3000 soft
braking can stop the motor quickly.
Extended saw band life because
torque shocks during start are
eliminated.
Easier saw band alignment. Slow
acceleration allows saw bands to
be ’tracked’ without jogging.
Maximum overload capability
available for ride through of
operating overloads. The
MCD3000 motor thermal model
Appl