Specifications

MCD3000 Series
MG.15.A4.22 - VLT is a registered Danfoss trademark 31
S
p
ecifications
General Technical Data
Mains supply (L1, L2, L3):
Supply voltage MCD3000-T5 ..............................................................................................3 x 200 VAC ~ 525 VAC
..................................................................................................... 3 x 200 VAC ~ 440 VAC (Inside Delta Connection)
Supply voltage MCD3000-T7 ............................................................................................. 3 x 200 VAC ~ 690VAC
..................................................................................................... 3 x 200 VAC ~ 440 VAC (Inside Delta Connection)
Supply frequency (at start) ....................................................................................... 50HZ (
± 2Hz) / 60 Hz (± 2Hz)
Supply frequency (during start) ........................................................ >45Hz (50Hz supply) or >55Hz (60 Hz supply)
Supply frequency (during run) ......................................................... >48Hz (50Hz supply) or >58Hz (60 Hz supply)
Electronics control voltage ......................................................... 230 VAC (+10%/-15%) or 400 VAC (+10%/-15%)
Control Inputs
Start (Terminals 15 & 16) .................................................................... Normally Open, Active 24 VDC, 8mA approx.
Stop (Terminals 17 & 18) ................................................................. Normally Closed, Active 24 VDC, 8mA approx.
Reset (Terminals 25 & 26) ............................................................... Normally Closed, Active 24 VDC, 8mA approx.
Parameter Set (Terminals 27 & 28) ..................................................... Normally Open, Active 24 VDC, 8mA approx.
Relay Outputs
Programmable Output A
1)
(Terminals 13 & 14) ...... Normally Open, 5 A @ 250 VAC/360 VA, 5 A @ 30 VDC resistive
Programmable Output B
2)
(Terminals 21, 22 & 24) .... Changeover, 5 A @ 250 VAC/360 VA, 5 A @ 30 VDC resistive
Output C
3)
(Terminals 33 & 34) .......................... Normally Open, , 5 A @ 250 VAC/360 VA, 5 A @ 30 VDC resistive
1)
Programmable functions: Line contactor, Run, High current flag, Low current flag
2)
Programmable functions: Tripped, Output on, High current flag, Low current flag, Line contactor
3)
Programmable functions: Run, D.C.Brake Contactor Control, Off
Environmental
Degree of protection MCD3007 to MCD3132 ................................................................................................. IP21
Degree of protection MCD3185 to MCD3800 ................................................................................................. IP20
Operating Temperatures ..................................................................................................................... -5
o
C / +60
o
C
Rated short-circuit current (with semi-conductor fuses) ................................................................................ 100kA
Rated insulation voltage (Surges) .......................................................................... 2 kV line to earth, 1kV line to line
Rated impulse withstand voltage (Fast transients) ............................................................................................. 2 kV
Pollution Degree ........................................................................................................................ Pollution Degree 3
Electro static discharge ......................................................................... 4 kV contact discharge, 8 kV air discharge
Equipment class (EMC) ............................................................................................................................... Class A
Radio-frequency electromagnetic field ...................................................................... 0.15 MHz - 80 MHz: 140dBµV
80 MHz - 1 GHz: 10 V/m
This product has been designed for Class A equipment. Use of the product in domestic environments may cause
radio interference, in which case the user may be required to employ additional mitigation methods.
Standards Approvals
Cá ......................................................................................................................................................... CISPR-11
UL
1
............................................................................................................................................................... UL508
C-UL
1
.............................................................................................................................................CSA 22.2 No. 14
CE .................................................................................................................................................. IEC 60947-4-2
1
Requires use of semi-conductor fuses. Excludes models MCD3600~MCD3800