Specifications

MCD3000 Series
= factory setting
28 MG.15.A4.22 - VLT is a registered Danfoss trademark
Pro
g
rammin
g
53 Expanded Supply Frequency Window
Value:
0 – 1
0
0 = Normal (50Hz window: 48Hz- 52Hz, 60Hz
window 58Hz – 62Hz)
1 = Expanded (50Hz window: 47Hz- 52Hz, 60Hz
window 57Hz – 62Hz)
Function:
Expands the supply frequency window allowed by the
MCD3000 by reducing the lower limit by 1 Hz. This
expansion accommodates power supplies which
suffer long term low frequency situations.
Description of choice:
Apply expansion if required.