Specifications
MCD3000 Series
✭ = factory setting
MG.15.A4.22 - VLT is a registered Danfoss trademark 17
Pro
g
rammin
g
■ Programming procedure
Parameter adjustments are made using the Local
Control Panel. Adjustments can only be made
while the MCD3000 is stopped. When the
MCD3000 is in programming mode the three LEDs to
the right of the numeric display are illuminated.
To adjust parameters do the following:
■
Programmable functions
1 Motor FLC
Value:
(Depends On Model) Amps
✭ Depends on Model
Function:
Calibrates the MCD3000 for the Full Load Current of
the motor.
Description of choice:
Set according to motor nameplate Full Load Current.
2 Current Limit
Value:
100% - 550% Motor FLC
✭ 350%
Function:
Sets the desired starting current limit.
Description of choice:
The current limit should be set so that the motor
accelerates easily to full speed.
ATTENTION
Start current must be great enough to allow
the motor to produce sufficient torque to
accelerate the connected load. The minimum current
required to do this is dependent on motor design and
load torque requirements.
3 Current Ramp - Initial Current
Value:
10% - 550% Motor FLC
✭ 350%
Function: