Specifications

MCD3000 Series
10 MG.15.A4.22 - VLT is a registered Danfoss trademark
Installation
Par. Set input. If there is an open circuit the primary
parameters (Par. 1 - 9) are operative. If there is a
closed circuit the secondary parameters (Par. 25 - 33)
are operative.
The MCD3000 provides three relay outputs.
Output A
24
22
21
14
13
34
33
Output B
Output C
Run
D.C.Brake contactor
Trip
Output on
High current flag
Low current flag
Line contactor
Line contactor
Run
High current flag
Low current flag
All outputs are programmable. Refer Par. 36, 37 & 38
Relay Function Assignment.
Motor thermistors
If the motor is fitted with thermistors these may be
connected directly to the MCD3000. A trip will occur if
the thermistor circuit resistance is above
approximately 2.8k
Ω.
If thermistors are not connected to the MCD3000
there must be a link across the thermistor input
terminals.
Control circuit examples
Example 1. A basic installation where motor operation
is controlled using the MCD3000 Local Control Panel.
Notes:
1. The MCD3000 must be in local mode to function
with this circuit. Use the [LOCAL/REMOTE] push
button to switch between local and remote
modes.