Installation Guide
Mounting Wiring Diagram
Web Configuration
BASpi-Edge is web page configurable and accessible from any PC with recent versions of most standard web browsers installed. To configure it initially, connect it to your
Windows PC using an Ethernet cable and set the PC’s IP address and subnet mask to the same subnet as the BASpi-Edge. Factory programmed:
IP Address: 192.168.92.68 Web server (HTTP) port: 80 (does not need to be typed in the browser address field)
Netmask: 255.255.255.0 Username: admin
Gateway: 192.168.92.1 Password: admin
ATTENTION: The default login password must be changed before the BASpi-Edge can be used or its system configuration altered. The password
must be at least 8 characters long and it must contain at least one letter and one number. This ensures authorized access to the BASpi-Edge only.
Reset IP address and login credentials: In the case that you cannot login to your BASpi-Edge, remove the clear top cover with label from the small side slit by using a
small screwdriver in order to access the RESET momentary switch (pictured in diagram above). Press and hold the switch for 10 seconds. Do not remove power. The unit will
enter Recovery Mode and will be accessible at its default IP address and login credentials in 30 sec. Your previous configuration will be shown in the System Configuration
page and could be changed or reused. Click Submit to apply settings. Click Restart Controller button to get back to normal operation.
Contemporary Control Systems, Inc. reserves the right to make changes in the specifications of the product described within this manual at any time without notice and without obligation of Contemporary Control Systems, Inc.
to notify any person of such revision or change.
BASpi-Edge is DIN rail or panel mounted. Only mount vertically with
respect to Earth. Do not mount horizontally. To DIN rail mount, simply
align and press against the DIN rail. To dismount, use a small screwdriver
to pry the DIN rail mount release tab down and pull the unit off the panel.
To panel mount, align the mounting hole on the back of the unit to the
screw on the panel (M4 or #8 screw) and slide down.