Instructions
CONTROLLINO Instruction Manual Page 7 (35)
Installation
For its proper use, CONTROLLINO PLCs must be mounted on a DIN rail, for example in a distribu-
tion box that is used for housing circuit breakers and relays and is commonly used in any home
installation.
• Electronic components of the product can become warm during operation. Take care to
prevent heat accumulation through proper air circulation around the unit.
• Do not mount the unit in insulating material or next to heat sources such as heating pipes,
radiators or electrical products such as motors or similar products. Mind the maximum
temperature specifications in the technical specifications!
• The product must not be operated or mounted in or under water.
• Be careful when drilling or tightening cables or wires in order not to damage them.
• During the mounting process, make sure that no moisture, water, dust or dirt gets inside
the housing. This might destroy the product!
• Mount the carrier system first, for example the distribution box.
• Arrange the CONTROLLINO controls and other assemblies in your overall application in the
distribution box. Installation is done simply by snapping the modules onto the DIN rail.
Important distances:
Distance from CONTROLLINO to front side of enclosure shall be min. 10 mm,
Distance from CONTROLLINO bottom to the bottom side of enclosure shall be 20 mm,
Distance from CONTROLLINO to another components min. 50 mm to other DIN rail.
Distance from CONTROLLINO to another components min. 0 mm on the same DIN rail.
Distance from CONTROLLINO to the enclosure min. 30 mm
• The unit can be in vertical or horizontal position.
• The unit shall be installed in enclosure which meets requirements for fire and electrical
enclosure.
• If necessary let your overall installation be checked by a competent person (electrician)!