Instruction Manual
Installer Menu
Revision E Display and Menu Options 3-29
28
0 = Disabled
1 = default
1 to 25 available
Configures the function of the user 2 output relay, which is
an electronic relay with the capacity for switching a DC
load only. The User 2 Relay is limited to 48 Volts DC and
4 Amps maximum load. Connect a device directly to the
two spade terminals at the bottom of the control board,
next to the label USER 2.
There are 25 optional logic function choices, which are
described in detail in
Setting the User Relay Function in the
Installer Menu
User 2 Relay
29
0 = 0 seconds
1 = 15 seconds
2 = 45 seconds
3 = 75 seconds
4 = 105 seconds
5 = 135 seconds
Adjusts the time delay before activating a user relay
function. Maximum time setting is 135 seconds. See
Setting
the User Relay Function in the Installer Menu
Note: This menu appears only when a user relay is set to
Function No. 8.
User relays
30
0 = 0 sec.
1 = 15 seconds
2 = 45 seconds
3 = 75 seconds
4 = 105 seconds
5 = 135 seconds
This function monitors activation of the Outside
Obstruction Loop when there is no activation of the gate.
When the adjustable period of time is exceeded, User Relay
No. 13 triggers and reports loitering in the diagnostics log.
Adjust the time delay before activating the user relay
function. Maximum time setting is 135 seconds. See
Setting
the User Relay Function in the Installer Menu
Note: This menu appears only when a user relay is set to
Function No. 13.
User relays
31
0 = No network
1 to 99 = Network “drop”
address
Sets the system address for network communication:
0 = no network communication
1-99 sets individual poling addresses.
RS-485
Table 3-2. Smart DC Controller - Installer Menu Functions (Continued)
Ref.
No.
*
Installer Menu
Setting Options
(
Bold = Factory Settings
)
Tasks and Explanations
Associated
DC Controller
Connections
Display
RL 2 1 CLOSE LIMIT
RELAY 2 LOGIC
TL 2 (45 SECS)
OPEN TIME ALERT
LT 3 (75 SECS)
LOITERING ALERT
SA 0 (OFF)
STC ADDRESS