Instruction Manual

Installer Menu
Revision E Display and Menu Options 3-25
13
0 = stop, reverse for 2s
1 = stop only
In a Usage Class 4 environment, the operator can be set to
stop the gate and not reverse gate travel after and IES trip.
Note: This menu option only appears when the Usage
Class is set to 4.
(N/A)
14
0 = none
1 through 20
For example:
1 = ½ second
4 = 2 seconds
20 = 10 seconds
Delays gate closure. This menu option appears if the gate
operator is designated as a Master or a Slave. Available
settings are 1 to 20. Each increment adds ½ second, to a
maximum of 10 seconds time delay, before the operator
activates when commanded to close.
DUAL GATE inputs on
both operators
15
0 = none
1 through 20
For example:
1 = ½ second
4 = 2 seconds
20 = 10 seconds
Delays gate opening. This menu appears if the gate
operator is set up as a Master or a Slave. Available settings
are 1 to 20. Each increment adds ½ second (with a
maximum of 10 seconds) time delay following a command
to open before the operator activates.
DUAL GATE inputs on
both operators
16
0 = 30 Seconds max run,
1 = 300 Seconds max run
Assigns a motor run time of 30 or 300 seconds. If the gate
opening or closure takes longer than 30 seconds, you’ll need
to set the run timer to 1.
(N/A)
Table 3-2. Smart DC Controller - Installer Menu Functions (Continued)
Ref.
No.
*
Installer Menu
Setting Options
(
Bold = Factory Settings
)
Tasks and Explanations
Associated
DC Controller
Connections
Display
SS 0 (OFF)
IES STOP ONLY
LC 0 (0.0 SECS)
LEAF DELAY CLOSE
LO 0 (0.0 SECS)
LEAF DELAY OPEN
RT 0 (30 SECS)
MAXIMUM RUN TIMER