Instruction Manual

Smart DC Controller Troubleshooting
6-22 SwingSmart DC Installation and Reference Manual Revision E
ERROR 4
MASTER-SLAVE COM
The Smart DC Controller has
detected a communication error in
the communication link between
master and slave in a dual gate
installation.
Several possible causes:
- Master/Slave communication cable has not been installed
correctly. See Chapter 5.
- Master/Slave not configured properly through the
Installer Menu.
- Operator not properly earth grounded.
- Master/Slave communication cable installed in same
conduit as high-voltage AC power.
- One operator does not have power applied to it.
One operator may have a different software version.
1. Correct communication cable.
2. Verify that each operator is configured
properly through the Installer Menu. One
operator must be set as Master and the other
operator must be set as Slave.
3. Install ground rod per NEC/NFPA standard.
4. Install separate conduit for communication
cables.
5. Ensure AC power is present at both operators
and both power switches are in the ON position.
6. Check the software version currently loaded in
the operator by pressing RESET. Make sure both
operators are running the same software version.
ERROR 5
No display
The display provides no indication
of this error, but it can appear in the
START log and means that the
Smart DC Controller has detected a
serious internal error.
Internal software /hardware error. Report any instance of
this error to HySecurity Engineering.
1. Turn both switches off to reset software.
2. Update to latest software version using START.
3. Replace Smart DC Controller.
ERROR 6 Not used in SwingSmart.
ERROR 7
MENU CHECKSUM
Software issue exists that may require
factory reset.
Corrupt software or data.
Call HySecurity Technical Support for assistance.
ERROR 8
RPM SENSOR
Not used in SwingSmart.
ERROR 9
BATTERY DISCONNE
The Smart DC Controller detected
there is no battery connected.
The batteries are disconnected, or a wiring fault exists.
SwingSmart operators ship with a wire disconnected to
prevent battery drain.
1.
Ensure the red wire in the upper left corner of
the electrical box is connected to the switch.
2. Correct any issues with battery wiring.
3. Check the 30 amp fuse on the circuit board.
ERROR 10
SLOWDOWN SWITCH
Not used in SwingSmart.
Table 6-1. Smart DC Controller - Troubleshooting