Instruction Manual

Smart DC Controller Troubleshooting
Revision E Reference 6-19
ALERT 5
BOTH LIM ACTIVE
Both limit switches are on at the
same time.
1. Stuck limit switch.
2. Short in wiring.
3. Debris in limit plate area.
1. Check limit switches and replace as required.
2. Check limit switch wiring, correct as
required.
3. Remove debris from limit area.
ALERT 6
LIM NOT RELEASED
The limit did not release when the
operator was commanded to move.
1. Taper clamp loose.
2. Broken drive belt.
3. Stuck Limit Switch.
4. Broken Limit Plate.
5. Debris in limit plate area.
1. Tighten Taper Clamp.
2. Check and replace drive belt.
3. Check limit switches and replace as required.
4. Check Limit Plate and replace as required.
5. Remove debris from limit area.
ALERT 7
FREQ SHIFT FAULT
The HY-5A has detected a frequency
change outside the normal range.
Likely causes are poor integrity of loops or metallic objects
within range. This message will also indicate which
detector the alert applies to: Exit Loop (ELD), Inside
Obstruction Loop (IOLD), Outside Obstruction Loop
(OOLD), or Center Loop (CLD).
The loop lead in wires and roadway should be
checked for problems or replaced.
ALERT 8
LOOP SHORTED
The HY-5A has detected a loop
shorted to ground.
Caused by inadequate insulation of loop wires. The loop lead in wires and roadway should be
checked for problems or replaced.
ALERT 9
LOOP OPEN
The HY-5A has detected a lack of
continuity in the loop wire.
Caused by broken loop wire or wire has come unplugged
from detector.
The loop and lead in wires should be checked
for problems or replaced.
ALERT 10
12C BUS ERROR
The Smart DC Controller has
detected a communication error
with a HY-5A vehicle detector.
Caused by removal of HY-5A or lack of integrity of the
socket connection. This message will also indicate which
detector the alert applies to: Exit Loop (ELD), Inside
Obstruction Loop (IOLD), Outside Obstruction Loop
(OOLD), or Center Loop (CLD).
Remove and re-install the HY-5A and press
RESET. Replace the HY-5A, if necessary.
ALERT 11
DETECTOR FAULT
The Smart DC Controller has
detected a problem within an HY-5A
vehicle detector.
Caused by a fault within the HY-5A. This message will also
indicate which detector the alert applies to: Exit Loop
(ELD), Inside Obstruction Loop (IOLD), Outside
Obstruction Loop (OOLD), or Center Loop (CLD).
Remove and re-install the HY-5A and press
RESET. Replace the HY-5A, if necessary.
ALERT 12
ON TOO LONG
The Smart DC Controller has an
active loop input (HY-5A or box
detector output) for more than 5
minutes.
Caused when the Smart DC Controller sees an active loop
for more than 5 minutes. The “active” loop can be actual or
false. This message will also indicate which detector the
alert applies to: Exit Loop (ELD), Inside Obstruction Loop
(IOLD), Outside Obstruction Loop (OOLD), or Center
Loop (CLD).
Check traffic patterns at the site. The loop and
lead in wires should be checked for problems or
replaced.
Table 6-1. Smart DC Controller - Troubleshooting
Display Description
Possible Causes Solutions
Condition Alert, Error or Fault