® ® US L I STED Pending UL325 compliant WWW.ALLOMATIC.NET OH-200DC Installation Manual Copyright © 2008 all-o-matic inc. www.allomatic.
TABLE OF CONTENTS Important safety instructions............................................................. 2 Different UL 325 class types........................................................ 3&4 Operator installation ........................................................................ 5 Operator mounting........................................................................... 6 Gate travel adjustment.....................................................................
IMPORTANT SAFETY INSTRUCTIONS WARNING To reduce the risk of injury: READ THE FOLLOWING DIRECTIONS. DO NOT EVEN THINK OF STARTING UNTIL YOU HAVE READ AND UNDERSTAND THESE DIRECTIONS. IF THERE IS SOMETHING YOU DO NOT UNDERSTAND CALL US. Never let children operate or play with gate controls. Keep the remote control away from children. Always keep people and objects away from the gate. No one should cross the path of the moving gate. This operator must be tested monthly.
INSTALL THE GATE OPERATOR ONLY WHEN YOU HAVE READ THE FOLLOWING: *Confirm that the gate operator being installed is appropriate for the application. *Confirm that the gate is designed and built according to current published industry standards. *Confirm that all appropriate safety features and safety accessory devices are being incorporated, including both primary and secondary entrapment protection devices. *Make sure that the gate works freely before installing the operator.
DIFFERENT UL 325 CLASS TYPES Class one: Residential A vehicle gate operator intended for use at a home of one to four single family dwellings, garages or parking area. Class Two: Commercial or General Public Access A vehicular gate operator intended for use at a commercial location or building such as a multi-family housing unit (five or more single family units), hotel, garages, retail stores, other buildings servicing the general public.
OPERATOR INSTALLATION Note: Make sure the gate hardware is well balanced and the gate opens and closes smoothly. With gate closed, mark the center of the gate. + Lift gate to open position and mark the center point of the gate for the operator on the ceiling.
MOUNTING THE OPERATOR + Center Weld Bolt Make sure end bracket is in the center of the opening. Bolt or weld the end bracket to wall. The operator bracket must be at least 2.5” above the gate. + Concrete Anchor ½”X 3 ½” Center Level and align gate operator before mounting it to the ceiling. Manufacture ceiling brackets to weld or bolt the operator in place. Gate Bracket Weld gate bracket into place with overhead arm connected to insure alignment.
GATE TRAVEL ADJUSTMENT Locate limit switches Step 1: Stop the gate operator using the three button station on the board. Step 2: Push limit lock plate down. Turn limit nut in the desired direction. Step 3: Place limit plate to its locked position. Step 4: Run gate operator. Step 5: If more adjusting is needed, repeat steps 1-4. Limit nuts Gear box Each notch equals about ½” of travel.
OPENING DIRECTION SETTINGS The OPEN L/R dipswitch Must be set to the ON position on this operator(OH-200DC). .01 I / 5W O O I0615 20M 1001 1001 6040 2402 MAAF S21B C8RB LMC64 82AIM 33 HFK 5GN F260 1212 3002 1001 UC3906DW U 74ZF2CW 602 SS26 602 SS26 1212 DR127-330 43CL07 E 1131 9531 ON 802 B 360G 4750 602 SS26 829B R616 802 B 360G ON SS 14 911C0 107A 100 HFK.
ELECTRICAL CONNECTION OPERATORS MUST BE PROPERLY GROUNDED! GRD LINE 1 LINE 2 V 230V 230 115V For power, a minimum of a 20-Amp dedicated circuit breaker is needed. For power wire enclosure use UL listed conduits. NOTE: When applying 230V to operator make sure voltage switch is flipped to 230V position. Power connection LINE 1 = LINE 2 = | 115VAC | 220VAC Single Phase 115V HOT 220V LINE 1 115V N 220V LINE 2 GND Connect to ground. Use a proper ground rod for a ground reference.
TYPICAL LOOP LAYOUT 8 FT 4 FT SAFETY LOOP 4 FT OUT 4ft from the tip of the point of gate swing. WIRED IN SERIES TWISTED 6 TURNS PER FOOT 1 1/2 IN 4 FT 8 FT SAFETY LOOP 1/4 IN EXIT LOOP 4 FT TWISTED WIRE TO OPERATOR OR CONTROL PANEL 4 FT GATE WHEN USED This is a normal loop layout. Remember when connecting to an All-O-Matic circuit board you use the normally closed contacts for your safety loop detector and normally open contacts from the exit loop.
GENERAL LOOP INSTALLATION GUIDELINES The following loop installation guidelines are for installing typical driveway loops for access control applications (i.e. parking gates, sliding gates, swing gates etc...) Always consult withl loop detector manufacturers for specific equipment guidelines. This will confirm that the proper configuration and installation techniques are properly applied for your application. Useful information about inductive loops: A.
ACCESSORY CONNECTIONS The circuit board 12-VDC output provides up to 500 mAmps of power for accessories. More than two or three accessories will require a separate power supply. NOTE: 12VDC Accessories only. 1002 710 KE. 710 KE. 7 10 KE. 7 10 KE. 1002 1002 1002 1002 2402 1001 ON 1001 1001 6040 1501 1501 1501 1501 1501 1501 1501 1501 1 50 1 MAAF S21B 1002 7 10 KE. 710 KE. 7 10 KE. 710 KE. 1002 C8RB LMC64 82AIM 1002 802 B 360G 7 10 KE.
MULTIPLE SAFETY DEVICES CONNECTIONS Multiple SAFETY devices installed together must be connected “in series”. Locate the normally closed (N.C.) dry contact from each accessory relay. Before installing the accessory devices, remove the wire jumper from the SAFETY position on the control board. Safety wire connections From Accessory #1 To Connecting pin From Accessory #2 To Connecting pin Relay Com Relay N.C. To COMMON To SAFETY From Accessory #1 to Accessory # 2 Relay N.C.
® LPR-1 LOOP RACK INSTALLATION This is a typical loop configuration for a gated driveway. Remember when connecting to an All-O-Matic circuit board the safety (reverse) uses normally closed contacts from the loop detector, the wire jumper from the safety connector needs to be removed when a safety loop is inatalled. You must twist your wires from your exit point of the saw cut all the way to the loop detectors, no exceptions.
LEADING EDGE CONNECTION 1002 1002 1002 710 KE. 710 KE. 7 10 KE. 7 10 KE. 1002 1002 2402 1001 ON 1001 1001 6040 1501 1501 15 01 1501 1501 1 50 1 1501 1501 1501 MAAF S21B 1002 7 10 KE. 710 KE. 7 10 KE. 710 KE. 1002 C8RB LMC64 82AIM 1002 802 B 360G 7 10 KE.
THREE BUTTON STATION SYSTEM See push button connections below. C8RB LMC64 O B U RNS 1001 1001 1 PHILIPS O B U RNS ON 802 B 360G 8 33 6 3 1001 1001 2262 RNS 2491 O B U C8RB LMC64 82AIM 1 8 33 6 3 100 HFK. 7J2 476E 900R3 911C0 476E 1AM 9 107A W107DIP - 3 MAGNECRAFT PHILIPS 104 Coilcraft F 3 71 0 KE. 8 33 6 1002 71 0 KE.
EMERGENCY RELEASE To manually release pull locking latch to the side and pull release ring downward with a slit pull backward to disengage from lock pin. Make sure gate is in full open position to avoid gate from coming down if not well balanced . Locking Latch Release Ring NOTE: To avoid serious injury disengage gate only when in the close position or gate is clear of persons and obstructions.
MAGNETIC/SOLENOID LOCK CONNECTIONS Magnetic lock installation requires a step down transformer with appropriate voltage for the specific lock accessory. Operator will provide a 120VAC outlet for the step down transformer. Connections: Plug the lock device transformer to the 120VAC outlet plug.
RADIO RECEIVER CONNECTIONS 3 wire receiver: mounts on receiver strip outside control box as shown below. 4 wire receiver: connect the two relay wires to 1 & 2 terminals. Black negative wire to terminal 1 and Red positive wire to terminal 3 on receiver strip outside control box as shown below. 1AM 9 1001 0618 R IOR IO 0618 829B R616 145 17 0 KE. IOR IR2110S IR2110S 710 KE.
OPEN AND CLOSE ELECTRONIC REVERSING SENSOR(ERDs) ADJUSTMENT Open and Close ERD SENSITIVITY .
TIMER ADJUSTMENT TIMER ON: Timer to close, can be set from 1 to 60 seconds. TIMER OFF: Gate operation is push button to open, push button to close. TO OVERRIDE THE TIMER: Turn the RADIO switch to the “ON” position. This will allow the radio receiver to close the gate before the timer. TIMER ADJUSTMENT Turn potentiometer counter clockwise for more time. 0 60 Sec Sec Turn potentiometer clockwise for less time. 0 60 Sec Sec .
DIP SWITCH FUNCTIONS OFF 1 TIMER switch “ON” activates the TIMER. See page 21 for details 2 . 3 4 RADIO RADIO switch “ON” allows the radio receiver to override the timer. See page 21 for details. 5 OSC 6 7 8 -----------------------OPEN------------------------ TIMER RADIO OSC FAIL SF/SC 1-PASS SLAVE AUTO OPEN OPEN L/R TIMER ON OSC switch “ON” allows the radio receiver to stop and reverse the gate in any direction. During a cycle the first signal stops gate, a second signal reverses gate.
SOLAR PANEL CONNECTION The solar panel input will take a 12VDC panel or two 12VDC panels wired in sires to make 24VDC . The charging circuit is limited by 1 Amp max. NOTE: For information on what solar panel to use on any other type of installation call ALL-O-MATIC for Assistance. 802 B 360G ON 20M 1001 1001 1001 3002 2402 6040 DR127-330 43CL07 E MAAF S21B 1212 C8RB LMC64 82AIM .
LED DIAGNOSTICS AC/PWR ON: Will be lit when AC power is ON. M/S LINK: Will be lit when master/slave communication is active. ALARM: Two states. 1st state: LED will blink(horn will beep also) every 30 seconds when battery is low, bad or disconnected. 2nd state: LED will turn on for 5 minutes when operator goes on shut down mode do to the gate hitting an obstruction(E.R.D.). Also, the horn will go off for 5 minutes. LOW BATTERY: Three states. 1st state: LED will be on solid when battery is low.
OVERHEAD DIMENSIONS 6 1\4 2 5/8’’’ 8’’ 4 1\2 Custom track length up to 16ft upon request.