Owner's manual
9050-065-M-3-11
28
DANGER
HIGH VOLTAGE!
5.1 Main Terminal Description
Low Voltage Common
Dry Relay Contact
Earth Ground
Circuit Board Power
Circuit Board Power
Motor
Motor
Built-In Solenoid
Lock Power
Full Open
Dry Relay Contact
Standard Reverse
• When gate is closed, this input will open gate to full position.
• When gate is open and auto close timer Switch 2
is turned ON, input will re-set and hold timer.
• When gate is open and auto close timer Switch 2
is turned OFF, input will close gate.
• When gate is closing, input will reverse gate.
• When gate is open and auto close
timer Switch 2 is turned ON, input
will re-set and hold timer.
• When gate is open and auto close
timer Switch 2 is turned OFF, input
will prevent gate from closing.
• When gate is closing, input will reverse gate.
• This input ONLY functions when gate is fully
open or in the closing cycle.
• Operation of relay is dependent on setting of switch 3.
• When Switch 3 is turned ON, relay activates
when gate is in the full open position.
• When Switch 3 is turned OFF, relay is
activated when gate IS NOT closed.
Relay contacts can be set for Normally Open (NO) or
Normally Closed (NC) operation.
Contact rating is 1 amp maximum at 24-volts DC.
8
NC
NO
4702-010
12
11
10
9
8
7
6
6
5
4
3
2
1
9
10
11
NC
NO
SECTION 5 - MAIN TERMINAL WIRING
24 VAC - 250 mamp. max.
1
ON
2 3 4 5 6 7 8
1
ON
2 3 4 5 6 7 8
1
ON
2 3 4 5 6 7 8