User's Manual

ITA ENG FRA ESP DEU POR
6 / 8
6-1620135 rev.1 08/07/2015
Through to the button on the RCOO900 it is possible, further than to carry out the programming of the TCOO900 (see paragraph 5), to carry out the
reset of the device deleting all the associated TCOO900. Proceed as follows to carry out the reset:
9. RCOO900 RESET
2
3
RCOO900 emits 1 BIP.
5
Release the key on the RCOO900.
Press and keep pressed the key on the
RCOO900.
DO NOT RELEASE the key on the RCOO900.
RCOO900 emits 6 BIP. The reset is ended.
1
RCOO900 emits 2 BIP.
4
DO NOT RELEASE the key on the RCOO900.
RCOO900 emits a series of close BIP.
DO NOT RELEASE the key on the RCOO900.
RCOO900 emits a continuos BIP.
The battery life is of about 2 years (5 years in Low Power modality). The TCOO900 keeps constantly under control the state of its batteries. When the
tension gets down under a pre – set value, this state is signaled to the associated RCOO900 which signals it (if the buzzer is active) with 4 BIP. If the
battery is not substituted, the TCOO900 will continue to regularly work until the tension of the batteries won’t get down under the minimum safety
threshold. If this happens, the RCOO900 will signal it with 5 BIP putting itself in state of alarm .
The device will remain in state of alarm until the battery of the transmitter won’t be substituted.
The substitution of the battery must be carried out by qualified personnel being necessary to open the TCOO900.
For each RCOO900 and relative TCOO900 it is possible to select a work frequency. This allows to be able to utilize up to a maximum of 4 RCOO900
on the same range of action without interferences.
For a correct functioning of the system it is indispensable that the frequency set on the RCOO900 corresponds to the frequency set on the
associated TCOO900. The selection of the frequency happens with DIP 3 and 4 on the RCOO900 and with DIP 4 and 5 on the TCOO900 as reported
on the following tables:
RCOO900
DIP 3 DIP 4
Frequency 1 ON ON
Frequency 2 ON OFF
Frequency 3 OFF ON
Frequency 4 OFF OFF
7. SELECTION OF THE WORKING FREQUENCY
8. FLAT BATTERY
TCOO900
DIP 4 DIP 5
Frequency 1 ON ON
Frequency 2 ON OFF
Frequency 3 OFF ON
Frequency 4 OFF OFF
6. SELECTION OF THE TYPE OF SIGNAL ON OUTPUT RELAY
Each relay has two different outputs. These outputs are:
1. N.C. contact (contact opens in case of alarm and closes if there is not alarm);
2. N.O. contact (contact closes in case of alarm and opens if there is not alarm) or a contact type 8K2 (resistance of the contact = 0 in case of
alarm and resistance of the contact = 8,2k if there is not alarm): the selection of the output type is through dip switches 5 and 6.
WARNING: in case of using 8k2 signal, the control unit connected to the device must be able to handle this type of signal.
The selection of the signal type is carried out in the following way:
OUTPUT SIGNAL USED TERMINAL
BOARD
SETTING OF
DIP SWITCH
N.C. contact
NC1-C1 (o NC2-C2) -
N.O. contact
NO1-C1 (o NO2-C2) DIP5 OFF (o DIP6 OFF)
8,2k resistive
NO1-C1 (o NO2-C2) DIP5 ON (o DIP6 ON)
8k2
8k2
1 2
3 4 5
6