User's Manual

ITA ENG FRA ESP DEU POR
3 / 8
6-1620135 rev.1 08/07/2015
DIP
Funzione
1 Mechanical (OFF) or resistive (ON) edge 1.
2 Mechanical (OFF) or resistive (ON) edge 2.
3 Low Power.
4
5
6
Mechanical edge with N.C. contact (OFF) or
Mechanical edge with N.O. contact (ON)
Selection frequency of functioning.
It is possible to associate up to a maximum of 8 T.CO.O900 to each RCOO900, while it is possible to associate up to a maximum of 8 different edges
to each relay.
WARNING: for a correct functioning of the system, every TCOO900 must have the frequency dip put on the same way as the
correspondent RCOO900.
On safety system with more than one RCOO900, to avoid interference, we recommend to set different frequency on different RCOO900 and the
associated TCOO900.
RCOO900
3. SETTINGS
TCOO900
DIP
ON
OFF
1
2
3
4
5
6
DIP
Funzione
1
Test device.
2 Buzzer ON / OFF.
3
4
5
NO1 output: N.O. contact (OFF) or 8k2
signal (ON) 1.
6
NO1 output: N.O. contact (OFF) or 8k2
signal (ON) 2.
Selection frequency of functioning.
DIP
ON
OFF
1 2
3
4
5
6
ATTENZIONE:
DIP1 OFF: mechanical safety edge 1
If you want to connect a mechanical element on
the input Safety1 (normally closed contact), you
must set dipswitch 1 on «OFF».
DIP2 ON: resistive safety edge 8,2k 2
If you want to connect a resistive element on the
input Safety2 (8k2 resistor), you must
set dipswitch 2 on «ON».
DIP6 OFF: mechanical safety edge N.C.
If you want to use a mechanical safety edge with
a normally closed contact , you must set dip
switch 6 on «OFF».
Dip switch
Resistive edge 2
Resistance 8,2k
Example: TCOO900 + 8,2k resistive edge 1 + Mechanical safety edge N.C. 2
Led and
programming /
test key 2
Led and
programming /
test key 1
F
Frequency
Low Power
Safety2 Type
Safety1 Type
Safety2
Safety1
Mechanical edge 1 (N.C.)
Led and
programming /
test key 2
Dip switch
Led and
programming /
test key 1
Mechanical edge 1 (N.O.)
Mechanical edge 2 (N.O.)
Example: TCOO900 + Mechanical safety edge N.O. 1 + Mechanical safety edge N.O. 2
F
Frequency
Low Power
Safety2 Type
Safety1 Type
Safety2
Safety1
1 2 3
4
5 6
1 2 3
4
5 6
WARNING:
DIP1 OFF: mechanical safety edge 1
If you want to connect a mechanical element on
the input Safety1 (normally closed contact), you
must set dipswitch 1 on «OFF».
DIP2 OFF: mechanical safety edge 2
If you want to connect a mechanical element on
the input Safety2 (normally closed contact), you
must set dipswitch 2 on «OFF».
DIP6 ON: mechanical safety edge N.O.
If you want to use a mechanical safety edge with a
normally open contact , you must set dip
switch 6 on «ON».