User's Manual

Table Of Contents
10.2 Door setting
Fail secure
(Unlocked when power on)
4 0 99 #
0-99 is to set the door relay time 0-99 seconds.
Fail safe (unlocked when power is off)
This is the factory default, 5 seconds:
5 0 99 #
0-99 is to set the door relay time 0-99 seconds.
Door open detection
Door Open Too Long (DOTL) warning. When used with an optional magnetic
contact or built-in magnetic contact of the lock, if the door is opened normally, but
not closed after 1 minute, the inside buzzer will beep automatically to remind
people to close the door and continue for 1 minute before switching off
automatically.
Door Forced Open warning. When used with an optional magnetic contact or
built in magnetic contact of the lock, if the door is forced open, or if the door is
opened after 120 seconds of the electro-mechanical lock not closed properly,
the inside buzzer and alarm output will both operate.
To disable door open detection.
(Factory default)
6 0 #
Security Mode Setting
Read er Lockout & Alarm Output options. If there are 10 invalid cards in a 10
minute period, the Reader will lockout for 10 minutes or the alarm will
operate for 10 minutes, depending on the option selected below.
Normal status (No lockout or alarm)
7 0 # (Factory default setting)
Reader Lockout
To Unlock the door
7 1 #
Alarm Output
7 2 #
Door Interlock.
Door interlock disabled
Door interlock enabled
8 0 #
8 1 #
Alarm output time
To set the alarm output time (0-3
minutes) Factory default is 1 minute
9 0~3 #
To remove the alarm
To remove the door forced open warning
Read valid card or Master Code #
To remove the door open too long
warning
Close the door or Read valid card
or Master Code #
Read user card (Note that Manager Card can't
be used to unlock the door.)
Attach: Advanced Application
1. W2 operating as a Controller
In this mode the W2 supports a Wiegand 26 bit input so an external Wiegand device
with a 26 bit output can be connected to the Wiegand input terminals on the W2.
Either an ID card reader (125 KHZ) or an IC card reader (13.56MHZ) can be
connected to the W2. Cards are required to be added at the external reader, except
where an external EM reader is used, in this case cards can be added at either
reader. See figure 1
figure 1
D0
D1
+12V
GND
-
+
Lock
-
+
Em card
HID card
Ic card
DC12V/3A
+
-
Power
D0
D1
ALARM-
OPEN
D_IN
+12V
GND
VSS
L-
L+
ALARM+
J1
Green
White
Grey
Yellow
Brown
Red
Black
Blue
Purple
Orange
wiegand reader
reader plug
W2 controller
Alarm
Exit button
door detecting switch
2. W2 operating as a Wiegand Output Reader
In this mode the W2 supports a Wiegand 26 bit output so the Wiegand data lines can
be connected to any controller which supports a Wiegand 26 bit input. See figure 2
ALARM+
J1
White
Grey
Yellow
Brown
Red
Black
Blue
Purple
Orange
D0
D1
W2
+
-
Powerful supply
Controller with wiegand 26 input
+12V
GND
Controller
Green
D0
D1
ALARM-
OPEN
D_IN
+12V
GND
VSS
L-
L+
figure 2
3. Two W2 units interconnected for a single door
In this mode two W2 units are used for a single door, one for entry and the other for exit.
Either device acts as the controller and reader at the same time. Users can be
enrolled oneither of the devices. In this mode the user capacity for one door can
be up to 20000. The setting of the two W2 units must be the same including the
master code. See figure 3
Exit button
-
+
Lock
door detecting switch
-
+
Alarm
DC12V/3A
+
-
Power
indoor
outdoor
D0
D1
ALARM-
OPEN
D_IN
+12V
GND
VSS
L-
L+
ALARM+
J1
Green
White
Grey
Yellow
Brown
Red
Black
Blue
Purple
Orange
D0
D1
ALARM-
OPEN
D_IN
+12V
GND
VSS
L-
L+
ALARM+
J1
Green
White
Grey
Yellow
Brown
Red
Black
Blue
Purple
Orange
W2 controller 2W2 controller 1
figure 3
4. Two W2 units interconnected & interlocked for 2 doors
In this mode two W2 units are used for a two doors which are then interconnected
and interlocked. In this mode the doors can be interlocked so that when door 1 is
open, door 2 cannot be opened, and vise versa. The interlocked function is mainly
used in banks, prisons, and other places where a higher level of security is required.
See figure 4
door detecting switch 1
-
-
+
+
Lock 1
-
+
-
+
DC12V/3A
+
-
Power
W2 controller 2
Door 2
Alarm 2
Alarm 1
Lock 2
Exit button 1
door detecting switch 2
Exit button 2
Door 1
W2 controller 1
D0
D1
ALARM-
OPEN
D_IN
+12V
GND
VSS
L-
L+
ALARM+
J1
Green
White
Grey
Yellow
Brown
Red
Black
Blue
Purple
Orange
D0
D1
ALARM-
OPEN
D_IN
+12V
GND
VSS
L-
L+
ALARM+
J1
Green
White
Grey
Yellow
Brown
Red
Black
Blue
Purple
Orange
figure 4
5. Anti-submarine function for single door (3 1 #)
The connection diagram is as figure 1. Install one Wiegand reader (or a W2
without user information as reader) outside the door, connecting to one W2-
Controller inside the door, which acts as the Anti-submarine Master unit. Of the
two devices, they build up an anti-submarine system for single door. The
operation and function is as below:
5.1 Set the needed function and enroll the User Cards on the inside W2 - Anti-
submarine Master unit.
5.2 With the valid user card, the user can only enter the door from the outside
reader, and exit from the inside W2 Controller. On the other hand, without
entering record from the reader, the user can't exit from the controller inside,
also, the user can't enter in and exit twice continuously.
6. Anti-submarine function for 2 doors
The connection diagram is as Figure 4. Door 1 with one W2, and Door 2 with
one W2, set one W2 on Door 1 as the Anti-submarine Auxiliary unit (3 2 #), and
set the other W2 on Door 2 as the Anti-submarine Master unit(3 1 #). They build
up a two doors anti-submarine system, which is normally used for parking
lot......etc
The operation and function is as below:
6.1 Set the needed function and enroll the User Cards from W2 - Anti-submarine
Master unit on Door 2.
6.2 With the valid user card, the user can only enter in from Door 1, and exit from
Door 2. On the other hand, without entering record from the Auxiliary unit, the
user can't exit from the Master unit or Auxiliary unit , also, the user can't enter in
and exit twice continuously.
.9. .10. .11.
.6. .7. .8.
Lock Power Setting
Anti-submarine Settings
Anti-submarine Disabled
Anti-submarine Master Mode:
Antisubmarine Auxiliary Mode
(Note: the detailed wiring diagram and illustrate,please refer to the Advanced application ) .
(Factory default)
3 0 #
3 1 #
3 2 #
To enable door open detection
6 1 #
To Unlock the door