CHAPTER 3 : Wiring the Terminal
20
3.8 Configuration information
The emerald terminal facilitates the use of a third party exit Wiegand head with three LEDs.
Power connections
The 12V power connections on J18 connect to the same common circuitry and are used to
provide power to the emerald terminal, as well as to output power to door furniture.
Typical Wiegand read head wiring
For specific read head wiring consult the third party manufacturer’s documentation.
Important
For proper regulatory compliance, the drain wire should be disconnected at the power supplied end of the cable.
Input configuration
The table below illustrates the configuration and operation of the terminal inputs when
configured with a third party Wiegand read head.
Note
Inputs are not for use as part of a burglar alarm system.
Inputs not in use
The door position input 0 must be shorted out between the IP0 and GND pins with wire when
not in use, to prevent alarms being generated on the system.
Ethernet cable ferrite
The ferrite must be attached to the Ethernet cable close to the exit point from the emerald
terminal. The cable should be looped through the ferrite once.
I/O board connection Typical HID colour
0V Black
Sounder Not Supported
LED Green Orange
LED Amber Not fitted
LED Red Brown
D1 White
D0 Green
Head 12V Red
Table 12: Typical Wiegand head wiring
Input number Input function Default input trigger state change
0 Door position short => open
1 Lock position short => open
2 Request to exit switch open => momentary short => open
3 Spare / Interlock short => open
Table 13: emerald and third party read head input configuration