7.4 Interlock
Interlocking terminals are linked together so that only one terminal will open its door at any
given time. This is achieved using a combination of wiring and software configuration.
Interlocking between two terminals is achieved using a simple wiring configuration, however
interlocking more than two terminals requires the use of a third party logic controller or
interposing relay system.
7.4.1 Wiring two terminals for interlock
Figure 54 Wiring two terminals for interlock
Software configuration for interlock
1. From the Floatbar open Device Configuration | Devices.
2. Select the terminal from the list and open the Configuration panel.