CHAPTER 7 : Door Modes
58
1. The card is swiped at the terminal and access granted.
2. Lock power is dropped for a period of time known as Lock open time. (Five second
default) If the door is not opened by the end of this time, the lock re-engages.
3. After the door is opened by the cardholder the lock power remains off for a period of time
to prevent the lock re-engaging and closing the door before it is fully opened. This is the
Lock open time 2. (One second default)
4. The door is closed. If the door remains open longer than the Door close after time a door
held alarm will be generated on the terminal and the AC2000 system. (Default 15 seconds)
Configuring the timings in the devices application
1. From the Floatbar open Device Configuration | Devices.
2. Select the terminal from the list and open the Configuration panel.
3. Open the Common panel.
Figure 46 Updating the door cycle timings
Note
Configuration of other timings is covered in the appendices of this manual.
7.1.2 Multi-swipe access
The emerald terminal can be configured to require swipes from up to five valid cards before
granting access. This is configured using the Device application. Once this setting is
Select the
timing which
is to be
amended
Update the
value
required in
seconds
Click Save