User's Manual
Table Of Contents
- Introduction
- Mounting the Terminal
- Wiring the Terminal
- 3.1 Cabling requirements
- 3.2 The Front Board
- 3.3 The Input/Output Board
- 3.4 Wiring locks
- 3.5 Terminal with Request to Exit Switch
- 3.6 Configuration information
- 3.7 Terminal with 3rd Party Wiegand Read Head
- 3.8 Configuration information
- 3.9 Terminal with S610s Exit Reader
- 3.10 Terminal with DIU 210
- 3.11 Terminal with DIU 230
- 3.12 PoE+ Terminal with S610s Exit Reader
- 3.13 Tamper Detection on Reader Inputs
- Reader Network Configuration
- AC2000 Software Configuration
- The System Configuration Menu
- Door Modes
- Appendix II: Device Settings Remote Application
- Appendix III: Broadcast and Timezone Priorities
- Appendix IV: Loading Card Definitions
- Appendix V: Configuring a Third Party Reader as a Master
A2SE67-UG-0011-1
CHAPTER 5 : AC2000 Software Configuration
42
Input table for emerald with S610s exit reader:
Input table for emerald with DIU210 and S610s exit reader:
Input number Input function Sensor state AED alarm
0 Door position Open Door forced
Closed Door closed
1 Lock position Open Lock not engaged
Closed Lock engaged
2 Request to exit No default
3 Spare / interlock No default
4 Spare No default
5 Spare No default
6 Spare No default
7 Spare No default
Table 23: emerald and S610s exit reader input alarms
Input number Input function Sensor state AED alarm
0 Door position Open Door forced
Closed Door closed
1 Lock position Open Lock not engaged
Closed Lock engaged
2 Request to exit No default
3 Break glass Open Breakglass
Closed Breakglass reset
4 Fire Open Fire alarm
Closed Fire alarm reset
5 Mains power fail Open Mains power fail
Closed Mains OK
6 Battery low Open DIU battery low
7 DIU tamper switch Open DIU tamper
8 Spare No default
9 Spare No default
A Spare No default
B Spare / interlock No default
C Spare No default
D Spare No default
E Spare No default
F Spare No default
Table 24: emerald and DIU210 input alarms