User's Manual
Table Of Contents
- Introduction
- Mounting the Terminal
- Wiring the Terminal
- 3.1 Cabling requirements
- 3.2 The Front Board
- 3.3 The Input/Output Board
- 3.4 Wiring locks
- 3.5 Terminal with Request to Exit Switch
- 3.6 Configuration information
- 3.7 Terminal with 3rd Party Wiegand Read Head
- 3.8 Configuration information
- 3.9 Terminal with S610s Exit Reader
- 3.10 Terminal with DIU 210
- 3.11 Terminal with DIU 230
- 3.12 PoE+ Terminal with S610s Exit Reader
- 3.13 Tamper Detection on Reader Inputs
- Reader Network Configuration
- AC2000 Software Configuration
- The System Configuration Menu
- Door Modes
- Appendix II: Device Settings Remote Application
- Appendix III: Broadcast and Timezone Priorities
- Appendix IV: Loading Card Definitions
- Appendix V: Configuring a Third Party Reader as a Master
AC2000 Getting Started Guide
25
3.10.1 Configuration information
Using a CEM DIU210 provides the highest level of security at a door, removing power for the
lock and input monitoring away from the door reader.
Important
The DIU210 uses mains electricity and should only be installed by qualified personnel.
Input configuration
When a DIU210 is used with a terminal, the DIU controls the main CEM reserved inputs and
the inputs on the readers become spare. The exception to this is input three on the terminal
(input B in Table 6 on page 13) which maintains its status as being used for interlock mode
.
Important
If a decision has been made not to connect a fire and break glass units to the DIU the inputs must be linked out to
ensure that the DIU functions normally. The tamper input must also be linked out when not in use to prevent
alarms being generated on AC2000.
Product CEM Product Code
DIU 200 (Compact board only DIU module) DIU/700/200
DIU 210 Full DIU incl Enclosure/PSU (Does
not include backup batteries)
DIU/700/210
Table 16: Door Interface Units product code
Input
number
Input
location
Input function Default input trigger state change
0 DIU Door position short => open
1 DIU Lock position short => open
2 DIU Request to exit switch open => momentary short => open
3 DIU Break glass short => open
4 DIU Fire short => open
5 DIU Mains power fail Internally triggered
6 DIU Battery low Internally triggered
7 DIU DIU tamper short => open
8Master
terminal
Spare short => open
9Master
terminal
Spare short => open
AMaster
terminal
Spare short => open
BMaster
terminal
Spare / Interlock short => open
C Exit reader Spare normally open
D Exit reader Spare normally open
E Exit reader Spare normally open
F Exit reader Spare normally open
Table 17: emerald and DIU210 input configuration