Chapter 3
Wiring the Terminal
3.1 Cabling requirements
Table 6 on page 13 outlines recommended cabling requirements for each of the connectors on
the emerald terminal.
3.1.1 Ethernet host
Ethernet communications should be cabled & terminated for 100Base-T operation according
to IN ANSI/TIA/EIA-568-A / TIA/EIA-568-B.
Due to limited space, additional care should be taken when using CAT6 connectors or CAT5
connectors with a strain relief boot at the terminal. There should be enough spare cable left
within the enclosure/back box to allow a service engineer to open the terminal case without
straining the RJ45 connector. Where the cable is subject to movement or vibration, stranded
ethernet cable (and appropriate connectors) should be used.
Purpose Recommended Cable Connector
Power over Ethernet & ethernet
comms
Cat 5/5e/6 RJ45
12V power supplied separately Recommend using a CEM Door
Interface Unit 210/230
14AWG Screw
Terminal
Inputs Belden 95XX or equivalent (XX =
the number of pairs from 01 - 50)
14AWG Screw
Terminal
Outputs Belden 9462 or equivalent 14AWG Screw
Terminal
Connection with exit reader or
DIU
Belden 8723 (AWG22 shielded
twisted 2-pair) or equivalent
14AWG Screw
Terminal
Wiegand Belden 9514 (7 x 22AWG), Alpha
1229C(9 x 22AWG) or equivalent
14AWG Screw
Terminal
Table 6: Terminal installation cabling requirements
Type Cable Connector Location
Host CAT5/CAT5e/CAT6 (PoE) RJ45 Socket Terminal board
Table 7: Ethernet host