User's Manual
Table Of Contents
- Introduction
- Mounting the Terminal
- Wiring the Terminal
- 3.1 Cabling requirements
- 3.2 The front board
- 3.3 The input/output board
- 3.4 Wiring locks
- 3.5 Terminal with Request to Exit switch
- 3.6 Configuration information
- 3.7 Terminal with third-party OSDPv2 read head
- 3.8 Terminal with third-party Wiegand read head
- 3.9 Terminal with DIU 230 and third-party Wiegand read head
- 3.10 Configuration information
- 3.11 S700e with S700s exit reader
- 3.12 S700 with DIU 210 and S700s exit reader
- 3.13 S700 terminal with DIU 230
- 3.14 Tamper detection on reader inputs
- Reader Network Configuration
- AC2000 Software Configuration
- The System Configuration Menu
- S700 Operational Modes
- Appendix 1 Updating Firmware
- Appendix 2 Broadcast and Timezone Priorities
- Appendix 3 Loading card definitions
S700 Installation Manual
97
Appendix 3 Loading card definitions
In order for AC2000 to correctly process the information encoded on the smart cards, the correct card
definitions must be loaded onto the CDC. These are loaded using the AC2000 Web pages.
1. Log into the AC2000 client software. This is done to allow access to the definition files on
the CDC.
2. Log into the web pages by opening a web browser.
3. Enter the Server IP Address, for example:
https://192.168.1.10
If the IP address has been changed from the default, enter the new IP address.
4. Enter the username and password.
5. Click Login.
6. Select AC2000 WEB, select System, and click Software Update.
7. Click Browse and navigate to Z:\\card_defs\patches.
8. Select the device image file (.cpio.bz) that is to be loaded.
Figure 70 Card definition file list
9. Click Upload
10. Click OK.