Updating the terminal
When the terminal has received the firmware file, the reader address is displayed in the colour
cyan instead of white.
Figure 68 Cyan reader address
To update the terminal, complete the following steps:
1. Access the System Configuration Menu of the terminal.
2. Press the number 8 on the keypad. This opens the Firmware Upgrade menu.
3. Select Apply.
Figure 69 Upgrading the terminal firmware
The reader updates and reboots.
Note: The reader goes offline for up to 30 seconds while the upgrade takes place.
Reader address
displayed in cyan