CHAPTER 7 : S700 Operational Modes
84
4. Clear the check box for Normal Input. Ensure the check box for Local output disabled is
selected.
Figure 58 Configuring input 3 for interlock
5. Select the Common tab.
6. Select Second swipe action.
Figure 59 Configuring interlock functionality
7. Select the No access on interlock and Make relay 0 active check boxes.
8. Click Close and click Save on the toolbar of the Devices application.