S700 Installation Manual
83
7.3.1 Wiring two terminals for interlock
Figure 57 Wiring two terminals for interlock
Software configuration for interlock
To configure the software for interlock, complete the following steps:
1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.
2. Select the terminal you want to configure and select the Properties tab.
3. Select the Input Config panel and select Input 3, or with DIU select Input B.