User's Manual

Table Of Contents
S700-IM-0088-1.72
CHAPTER 7 : S700 Operational Modes
76
Table 30: Illustration of door timings
The following steps outline the door open cycle:
1. The valid card is swiped at the terminal and access is granted.
2. Lock power is dropped for a period of time known as Lock open time: five second default.
If the door is not opened by the end of this time, the lock re-engages.
3. After the door is opened by the cardholder the lock power remains off for a period of time
to prevent the lock re-engaging and closing the door before it is fully opened. This is the
Lock open time 2. The default for this is one second.
4. The door is closed. If the door remains open longer than the Door close after time, a door
held alarm is generated on the terminal and the AC2000 system. The default is 15
seconds.
Configuring the timings in the Devices application
To configure timings in the Devices application, complete the followings steps:
1. Log on to the AC2000 Floatbar, click Device Configuration, and click Devices.
2. Select the terminal you want to modify and select the Properties tab.
Lock output
Lock Open
Time
Lock Open Time
Normal open
Door close after
Sounder
warning,
legal open
time
running out
Pre-alarm
Allowing time
to close
Close time
Door held
alarm and
alarm
sounder
Alarm Time
Notes If the door is not
detected
open before
the Lock
Open Time
period
expires, the
lock is re-
secured and
the door
mode returns
to the idle
state
The door has
been
detected
open
If the door is
detected
closed before
the Door
close after
period, the
Lock Open
Time 2 is
cancelled
and the door
mode returns
to the idle
state
The pre-alarm
starts the
defined
second
before Door
close after
expires
Close Time
is to allow
an
automatic
door time
to close
when the
cycle is
complete;
the pre-
alarm
continues
during the
Close
Time