User's Manual
Table Of Contents
- Introduction
- Mounting the Terminal
- Wiring the Terminal
- 3.1 Cabling requirements
- 3.2 The front board
- 3.3 The input/output board
- 3.4 Wiring locks
- 3.5 Terminal with Request to Exit switch
- 3.6 Configuration information
- 3.7 Terminal with third-party OSDPv2 read head
- 3.8 Terminal with third-party Wiegand read head
- 3.9 Terminal with DIU 230 and third-party Wiegand read head
- 3.10 Configuration information
- 3.11 S700e with S700s exit reader
- 3.12 S700 with DIU 210 and S700s exit reader
- 3.13 S700 terminal with DIU 230
- 3.14 Tamper detection on reader inputs
- Reader Network Configuration
- AC2000 Software Configuration
- The System Configuration Menu
- S700 Operational Modes
- Appendix 1 Updating Firmware
- Appendix 2 Broadcast and Timezone Priorities
- Appendix 3 Loading card definitions
S700-IM-0088-1.72
CHAPTER 3 : Wiring the Terminal
40
Note: To configure an exit reader as the master reader, see Configuring a Third-Party Reader
as a Master on page 85.
Important: For regulatory compliance, the drain wire must be disconnected at the reader-end of
the cable.
Table 12: Configuration and operation of terminal inputs contains the details for the
configuration and operation of terminal inputs when configured with third-party Wiegand read
heads.
Table 12: Configuration and operation of terminal inputs
Important: If fire and break glass units are not required, the inputs must be connected to GND
to ensure that the DIU functions normally. The tamper input must also be connected to the
GND when it is not in use to prevent alarms being generated on AC2000.
3.9.1 Software configuration for terminal with DIU 230 and third-party
Wiegand read head
To configure AC2000 for use with the terminal, a DIU 230 and a third-party Wiegand read
head, complete the following steps:
1. Add the device in the Devices application as S700+DIU+Slave. For more information on
the procedure for adding a device, see Adding the device to AC2000 on page 56.
2. Enable the third-party read head. For more information on the procedure for enabling a
third-party read head, see Configuring a third-party read head on page 57.
3.10 Configuration information
The S700 terminal facilitates the use of a third-party exit Wiegand head with three LEDs.
Supported third-party read heads
CEM support the use of HID R10 heads for reading Mifare and iClass cards.
Input
number
Input location Input function Default input trigger state function
0 DIU Door position short => open
1 DIU Lock position short => open
2 DIU Request to exit switch open => momentary short => open
3 DIU Fire short => open
4 DIU Breakglass short => open
5 DIU Mains power fail Internally triggered
6 DIU Battery low Internally triggered
7 DIU DIU tamper short => open
8 Master terminal Spare short => open
9 Master terminal Spare short => open
A Master terminal Spare short => open
B Master terminal Spare/Interlock short => open