User's Manual
Table Of Contents
- 1 Introduction
- 2 Quick Guide to setting up S610S
- 3 Connecting an S610S Master Reader
- 3.1 Open the S610 reader case
- 3.2 S610S Master Reader 12V Power and Data connections
- 3.3 Extra settings required, made on the reader
- 3.4 Addressing an S610S master reader
- 3.5 S610S Connecting Master Reader Inputs
- 3.6 Monitoring Inputs for Cable Tampers
- 3.7 Using an external read head
- 3.8 S610S Lock and spare output relay connections
- 4 Connecting an S610S to an Exit Reader
- 5 Connecting an S610S to a DIU
- 6 AC2000 Devices Application tasks
- 7 Door Modes
- 8 Interlock
- 9 Other AC2000 software configurations
- 10 S610S onboard diagnostic mode
- 11 Appendix
S610S Manual - Hardware Installer Manual - Version 1.8
28
Door time zone - Select, then Edit to apply the Time Zone you have created for DOOR OVERRIDE,
the door will be unlocked during this Time Zone. Read heads are disabled and door input alarm
monitoring is disabled.
Master t/s time zone - Edit, to disable Master Turnstile during this Time Zone
Slave t/s time zone - Edit, to disable Slave Turnstile during this Time Zone
Time Zone Active
- Enable if you want to used Extended Time Zone mode.
WHAT IF THE READER IS OFFLINE ?
The settings described above are also stored on the reader, so if a reader becomes off line, the time
zone operations will remain in place, and access control continues as programmed. If Door
Override is configured to open a door for a set Timezone then the door will continue to unlock
when the reader is off line. A broadcast to open a door, while a reader is off line will fail.
For PIN ONLY see paragraph 7.7 PIN Only, in this manual.
For options to separate Master and Exit PIN requirements see 7.8, Extended Timezone
configuration.
6.6 Extended Timezone configuration
Introduced to the S600S reader firmware version1.00.034. Extended time zone allows access
control between Master and Exit reader to differ according to Timezone settings. It is not possible
to have different time zones applied to each Master and Exit reader.
For example: between 9am to 5pm PIN only may be required to gain access at the reader, but after
hours, a CARD+PIN would be required to gain access, but to leave the area it can be always PIN
ONLY.
Shows Device Configuration – Door Time Zone.
Above, Extended Time Zone settings apply to this configured Time Zone.
Using AC2000 workstation Devices application, select a configured S600 type reader.
From the
Configuration table filter TimeZones, select Time Zone Active.
If needed the function will need to be
Enabled.
TIME ZONE ACTIVE
See Door Time Zone above.
S610S Time Zone Active options group.
Master locked - For the duration of Door Time Zone the Slave reader will respond, but Master read
head and keypad are disabled.
Slave Locked - For the duration of Door Time Zone the Master reader will respond, but Slave read
head and keypad are disabled.
Master and Slave Locked - This option will LOCK DOOR and disable read head and keypad for the
duration of Door Time Zone.
Door Override - This option will UNLOCK DOOR for the duration of Door Time Zone. The read
head and keypad are disabled.