S610S Manual - Hardware Installer Manual - Version 1.8
24
Lock open time - (Sec) Maximum time to release the lock after a valid card presentation
Lock open time2 - (Sec) Time lock stays de-energised after a door is opened.
Try
LockOpenTime 2 if interleaved double doors are used. This additional time setting allows the
second door to open before the door’s locks re-engage. Normally door locks will re-engage as soon
as the first door is opened, locking the second door before it has opened.
Door close after - (sec) Maximum time for door to remain open before a door holder releases the
door.
Close Time - (sec) After Door Close After has passed a door has this time to close, this allows a
door to slowly swing shut after a door has released it, avoiding an unnecessary alarm..
Pre Alarm - (sec) The time duration the Pre Alarm sounder on the reader will sound. The alarm
warns a person to close the door before an actual alarm is reported to the system.
Alarm Time - (sec) The time duration the sounder on the reader will sound
Debounce - (.5 sec) Settling time after a door has closed. Debounce avoids a door forced alarm
when a door bounces open before finally remaining closed.
Display on time - (sec) Time the LCD backlight remains lit after a transaction or alarm.
PIN time - (sec) Time allowed to enter a PIN
Passenger Time - (sec) Maximum time for door to remain open in Passenger Mode before a door
holder will release it.
Occupancy swipe time - (sec) - automatic equipment disable period (if LockOpenTime2 =0)
Confirmation Time(sec) Retinal scan setting – not supported by S610S readers
AC2000 Door Mode door cycle time sequence of events.
6.3 Changing other reader settings
Configuration status - enable Smart Keys special card defs etc
Output level - Use these options to invert a selection of outputs
Input level - Use these options to invert a selection of inputs
Second swipe action - Use to configure reader action when a second card swipe at the reader occurs,
while the first card swipe action is still active.
Global Pin - Set a pin number for this reader, the same PIN will be used by all for access during a
PIN only Timezone.
Database size - used to change the off line data record set held on the reader
Site code - Used to change a site code on a reader. A special option only used if extended access
control encompasses a new set of cards with a site code different from normal. Only cards with this
site code will be valid on this reader.
Site code position - Only used for BAMC LED codes on Broadcast.
CONFIGURATION STATUS
Enable RTD mode - Passenger lock open time must be triggered by a Oneshot from RTD
Enable Card Definitions - check if using downloadable card definitions.
Enable smart keys - Check if Pico or embedded keys are used on the card type.
Enable messages - this must be checked if custom Reader Messages are to be down loaded to this
reader. See manual on AC2000 Reader Messages, workstation application.
Lock Open Time
(Secs)
LOT2
(Secs)
Door Close After (Secs)
Door
Opened
Close Time (Secs)
Card Swipe
Door Holder
Releases
Door Holder
Engaged
END OF CYCLE
Pre Alarm (Secs)
Alarm Time
(Secs)
Door held
alarm
generated
315
5
0