S610S Manual - Hardware Installer Manual - Version 1.8
18
Devices Application - Setting the S610S Exit reader configuration
Wire an Exit reader to the master as shown above.
A Master reader does not automatically connect to the Exit Reader or DIU.
The Master reader’s configuration must be updated to include an Exit Reader on the AC2000
workstation Devices Application.
Shows the AC2000 Devices application, Device Type, being updated.
Select S600+DIU+Slave if a DIU and Exit reader are present.
4.2 S610S Master with Slave input connection table
AC2000 Workstation Connector on
S610S
Reader
J6
Description
Devices
application
INPUT #
Input Configuration
Normal setting
Checked/Unchecked
Master S610S Reader
IP 0 Unchecked J6 Pin IP0 Door position sensor
IP 1 Unchecked J6 Pin IP1 Lock Status Sensor
IP 2 Unchecked J6 Pin IP2 Request to Exit button
IP 3 Checked
(Uncheck for Interlock)
J6 Pin IP3 Interlock control or GP
Exit/Slave S610S Reader
IP 4 Checked J6 Pin IP0 GP
IP 5 Checked J6 Pin IP1 GP
IP 6 Checked J6 Pin IP2 GP
IP 7 Checked J6 Pin IP3 GP
NOTE: A Normal or Checked setting means the Input is free for GP Use
NOTE: A GP (General Purpose) input AED alarms can be customised using AC2000 software
Devices and Alarm Config application. See AC2000 Devices and Alarm Config manuals for
further information. Connecting S610S with DIU
For more information on using a DIU please consult the relevant DIU manual.