User's Manual
Table Of Contents
- 1 Introduction
- 2 Quick Guide to setting up S610S
- 3 Connecting an S610S Master Reader
- 3.1 Open the S610 reader case
- 3.2 S610S Master Reader 12V Power and Data connections
- 3.3 Extra settings required, made on the reader
- 3.4 Addressing an S610S master reader
- 3.5 S610S Connecting Master Reader Inputs
- 3.6 Monitoring Inputs for Cable Tampers
- 3.7 Using an external read head
- 3.8 S610S Lock and spare output relay connections
- 4 Connecting an S610S to an Exit Reader
- 5 Connecting an S610S to a DIU
- 6 AC2000 Devices Application tasks
- 7 Door Modes
- 8 Interlock
- 9 Other AC2000 software configurations
- 10 S610S onboard diagnostic mode
- 11 Appendix
S610S Manual - Hardware Installer Manual - Version 1.8
7
How to use an S610S reader
Swipe a card over the keypad area, then enter a keypad command or PIN if required to do so.
LED Card Response table
Green Card Valid Description
Flashing Green Card Expiring Consult System Admin to extend Card Expiry date
Amber Wrong Zone
Wrong Time zone
Passback failure
Wrong PIN
Door not in card holder’s Access Level.
Door is in Card Holders Access level but not Time Zone.
Card holder must comply with site access policy.
Swipe again and enter correct PIN.
Red – Invalid card
Flashing Red
Card error - retry
Card not in system
Card expired
Lost or Stolen Card
Try again; if fault persists consult your system administrator.
Consult your system administrator or site security office.
Consult your system administrator or site security office.
Consult your system administrator or site security office.
1.1 Cabling requirements
Cable needed Connector type
2 pair (Belden 8723) cable, DataA, DataB, GND and 12V 4 way JST – J15
6 pair (Belden 8723) maximum Inputs and
Outputs
8 way JST – J6 and
6way socket – J12
2 pair (Belden 8723) power/comms to Exit reader 4 way JST – J5 to J5