InfoProx Entry Technical Description
Power Connector
Power is supplied to the board via connector J3. Figure 9 shows the layout of the
connections:
1
2
3
4
J3
+
-
Power in
7 - 15V DC
Figure 9: Power Connector with Nominal 12V DC Power Supply
Power for the reader can be supplied locally, using a Door Interface Unit or a 12V
DC power supply.
Reader Inputs & Outputs
For standard door mode the following applies: input 0 monitors door position; input
1 monitors lock status; input 2 is for push button; and input 3 is a spare unit.
However, these defaults can be overwritten.
The reader has one relay, rated at 30VDC @ 5 Amps. In normal door mode, this
relay is reserved for door strike, such as relay automatically fires on a valid card
swipe. The four inputs and the relay output for the reader are connected in the ten-
way Phoenix Contact J2.
Exit Reader Connections
The full exit reader connects to the entry reader through an RS485 port. The
connection is made from connector J3 on the master reader to connector J3 on
the exit reader.
A
B
+
-
J3
Power in
7 - 15V DC
RS485 Data
to/from exit
A
B
+
-
J3
Figure 10: Exit Reader Connections
Software House 65