User's Manual

22 23
Setup and testing
HVAC Installer system settings table
System setting Description
Factory default setting
(bold) and setting range
06. Heat/Cool:
Fan Control in
Heating
Heat Pump:
Auxiliary
Equipment Type
Heat/Cool: Determines if the thermostat or
equipment controls the fan in heating.
Heat Pump: Auxiliary equipment type.
Gas/Oil Heat
(Equipment Controls Fan)
Electric Heat
(Thermostat Controls Fan)
07. Extended Fan—
Heat
Extends the fan run time after a heat call ends. Disable
Enable (90 second extension)
08. Extended Fan—
Cool
Extends the fan run time after a cool call ends. Disable
Enable (90 second extension)
09. Internal
Temperature
Sensor Oset
Field adjustment of internal temperature
sensor.
(no oset applied)
-4°F to +4°F (-2°C to +2°C)
10. Internal RH Sensor
Oset
Field adjustment of internal humidity sensor. 0% (no oset applied)
-5% to +5%
11. Auto Changeover Enables or disables the option of setting
the system mode to Auto. When the system
mode is set to Auto, the thermostat can
automatically switch between heating and
cooling to maintain a room temperature that is
between the heat and cool setpoints.
Disable
Enable
12. Deadband Auto season changeover deadband. 3°F or 1.5°C
2°F to +9°F (1°C to 4.5°C)
HVAC Installer system settings table
System setting Description
Factory default setting
(bold) and setting range
13. Remote Sensor Selects if the wired remote sensor is installed. No
Yes
14. Primary Sensor Selects the primary sensor to be used for
temperature control.
Built In
Remote
15. Secondary Sensor Selects the sensor to be used for control if
the primary sensor fails. Remote will only be
presented as an option if Remote Sensor is
set to Yes.
None
Remote
Built In
16. Outdoor Sensor Selects if an outdoor sensor is installed or if
the thermostat receives an outdoor sensor
value from the Control4 system.
Not Installed
Wired
Control4 Value
17. Compressor Min O
Time
Minimum o time for compressor protection. 5 minutes
1 to 5 minutes
18. Heating Min O
Time
Minimum o time for heating. 2 minutes
1 to 5 minutes
19. Equipment Min On
Time
Minimum on time for heating or cooling. 2 minutes
1 to 5 minutes
20. Auto Changeover
Time
Minimum time between heating and cooling
calls.
4 minutes
1 to 5 minutes