The tables below give the definition of variable minimum/maximum and the maximum range of these.
VM_AC_VOLTAGE Range applied to parameters showing AC voltage
Units V
Range of [MIN] 0
Range of [MAX] 0 to the value listed below
Definition
VM_AC_VOLTAGE[MAX] is drive voltage rating dependent. See Table
VM_AC_VOLTAGE[MIN] = 0
VM_AC_VOLTAGE_SET Range applied to the AC voltage set-up parameters
Units V
Range of [MIN] 0
Range of [MAX] 0 to the value listed below
Definition
VM_AC_VOLTAGE_SET[MAX] is drive voltage rating dependent. See Table
VM_AC_VOLTAGE_SET[MIN] = 0
VM_ACCEL_RATE Maximum applied to the ramp rate parameters
Units s / 100 Hz
Range of [MIN] 0.0
Range of [MAX] 0.0 to 99999.9
Definition 0.0 to 99999.9
VM_DC_VOLTAGE Range applied to parameters showing DC voltage
Units V
Range of [MIN] 0
Range of [MAX] 0 to the value listed below
Definition
VM_DC_VOLTAGE[MAX] is the full scale d.c. jumper voltage feedback (over voltage trip level) for the drive. This level
is drive voltage rating dependent. See Table
VM_DC_VOLTAGE[MIN] = 0
VM_DC_VOLTAGE_SET Range applied to DC voltage reference parameters
Units V
Range of [MIN] 0
Range of [MAX] 0 to the value listed below
Definition
VM_DC_VOLTAGE_SET[MAX] is drive voltage rating dependent. See Table
VM_DC_VOLTAGE_SET[MIN] = 0
VM_DRIVE_CURRENT Range applied to parameters showing current in A
Units A
Range of [MIN] -9999.99 to 0.00
Range of [MAX] 0.00 to 9999.99
Definition
VM_DRIVE_CURRENT[MAX] is equivalent to the full scale (over current trip level) for the drive and is given by Full
Scale Current Kc (11.061).
VM_DRIVE_CURRENT[MIN] = - VM_DRIVE_CURRENT[MAX]
VM_DRIVE_CURRENT_UNIPOLAR Unipolar version of VM_DRIVE_CURRENT
Units A
Range of [MIN] 0.00
Range of [MAX] 0.00 to 9999.99
Definition
VM_DRIVE_CURRENT_UNIPOLAR[MAX] = VM_DRIVE_CURRENT[MAX]
VM_DRIVE_CURRENT_UNIPOLAR[MIN] = 0.00