60 Unidrive M100 User Guide
Issue Number: 1
6.2 Parameter descriptions
6.2.1 Pr mm.000
Pr mm.000 is available in all menus, commonly used functions are provided as text strings in Pr mm.000 shown in Table 6-1. The functions in Table
6-1 can also be selected by entering the appropriate numeric values (as shown in Table 6-2) in Pr mm.000. For example, enter 7001 in Pr mm.000 to
store drive parameters on an NV media card.
Table 6-1 Commonly used functions in xx.000
Table 6-2 Functions in Pr mm.000
* See Chapter 9 NV Media Card Operation on page 78 for more information on these functions.
** These functions do not require a drive reset to become active.
All other functions require a drive reset to initiate the function. To allow easy access to some commonly used functions, refer to the table overleaf.
Equivalent values and strings are also provided in the table above.
Value Equivalent value String Action
00
None No action
1000 1
SAVE Save drive parameters to non-volatile memory
6001 2
read1
Load the data from file 1 on a non-volatile media card into the drive provided it is a
parameter file
4001 3
SAVE1 Store the drive parameters in file 1 on a non-volatile media card
6002 4
read2
Load the data from file 2 on a non-volatile media card into the drive provided it is a
parameter file
4002 5
SAVE2 Store the drive parameters in file 2 on a non-volatile media card
6003 6
read3
Load the data from file 3 on a non-volatile media card into the drive provided it is a
parameter file
4003 7
SAVE3 Store the drive parameters in file 3 on a non-volatile media card
12000 8
diff.d Only display parameters that are different from their default value
12001 9
dest Only display parameters that are used to set-up destinations
1233 10
def.50 Load 50 Hz defaults
1244 11
def.60 Load 60 Hz defaults
Value Action
1000 Save parameters when Under Voltage Active (Pr 10.016) is not active.
1001 Save parameter under all conditions
1233 Load standard (50 Hz) defaults
1234 Load standard (50 Hz) defaults to all menus except option module menu 15
1244 Load US (60 Hz) defaults
1245 Load US (60 Hz) defaults to all menus except option module menu 15
1299 Reset {St.HF} trip.
2001* Create a boot file on a non-volatile media card based on the present drive parameters
4yyy* NV media card: Transfer the drive parameters to parameter file xxx
5yyy* NV media card: Transfer the onboard user program to onboard user program file xxx
6yyy* NV media card: Load the drive parameters from parameter file xxx or the onboard user program from onboard user program file xxx
7yyy* NV media card: Erase file xxx
8yyy* NV Media card: Compare the data in the drive with file xxx
9555* NV media card: Clear the warning suppression flag
9666* NV media card: Set the warning suppression flag
9777* NV media card: Clear the read-only flag
9888* NV media card: Set the read-only flag
9999* NV media card: Erase and format the NV media card
12000** Only display parameters that are different from their default value. This action does not require a drive reset.
12001** Only display parameters that are used to set-up destinations (i.e. DE format bit is 1). This action does not require a drive reset.