User guide
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization NV Media Card
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
34 Unidrive M100 User Guide
Issue Number: 1
Table 4-3 AC Input current and fuse ratings (100 V)
Table 4-4 AC Input current and fuse ratings (200 V)
Table 4-5 AC Input current and fuse ratings (400 V)
Ensure cables used suit local wiring regulations.
Fuses
The AC supply to the drive must be installed with suitable protection against overload and short-circuits. Table 4-3 shows recommended
fuse ratings. Failure to observe this requirement will cause risk of fire.
WARNING
Model
Typical input
current
Maximum
continuous
input current
Maximum
overload input
current
Fuse rating
IEC gG Class CC or Class J
Maximum Maximum
AAA
AA
01100017 8.7 8.7 10 10
01100024 11.1 11.1 16 16
02100042 18.8 18.8 20 20
02100056 24.0 24.0 25 25
Model
Typical input
current
A
Maximum
continuous
input current
A
Maximum
overload input
current
A
Fuse rating
IEC gG Class CC or Class J
Maximum
A
Maximum
A
1ph 3ph 1ph 3ph
01200017 4.5 4.5
6
5
01200024 5.3 5.3
10
01200033 8.3 8.3 10
01200042 10.4 10.4 16 16
02200024 5.3/3.2 5.3/4.1 6 10 5
02200033 8.3/4.3 8.3/6.7 10 10
02200042 10.4/5.4 10.4/7.5 16 10 16 10
02200056 14.9/7.4 14.9/11.3
20 16 20 16
02200075 18.1/9.1 18.1/13.5
03200100 23.9/12.8 23.9/17.7 25 20 25 20
04200133 23.7/13.5 23.7/16.9 25 20 25 20
04200176 17.0 21.3
25 25
Model
Typical input
current
Maximum
continuous input
current
Maximum
overload input
current
Fuse rating
IEC gG Class CC or Class J
Maximum Maximum
AAA
AA
02400013 2.1 2.4
6
502400018 2.6 2.9
02400023 3.1 3.5
02400032 4.7 5.1
10
02400041 5.8 6.2 10
03400056 8.3 8.7 10 10
03400073 10.2 12.2
16
16
03400094 13.1 14.8 20
04400135 14.0 16.3 20 20
04400170 18.5 20.7 25 25
NOTE