User guide

Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization NV Media Card
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
Unidrive M100 User Guide 29
Issue Number: 1
3.10 Routine maintenance
The drive should be installed in a cool, clean, well ventilated location. Contact with moisture and/or dust with the drive should be avoided.
Regular checks of the following should be carried out to ensure drive / installation reliability are maximized:
Environment
Ambient temperature Ensure the enclosure temperature remains at or below maximum specified
Dust
Ensure the drive remains dust free – check that the heatsink and drive fan are not gathering dust.
The lifetime of the fan is reduced in dusty environments
Moisture Ensure the drive enclosure shows no signs of condensation
Enclosure
Enclosure door filters Ensure filters are not blocked and that air is free to flow
Electrical
Screw connections Ensure all screw terminals remain tight
Crimp terminals
Ensure all crimp terminals remains tight – check for any discoloration which could indicate
overheating
Cables Check all cables for signs of damage