Unidrive M100 User Guide 131
Issue Number: 1
OV DC bus voltage has exceeded the peak level or maximum continuous level for 15 seconds
2
The OV trip indicates that the DC bus voltage has exceeded the VM_DC_VOLTAGE[MAX] or
VM_DC_VOLTAGE_SET[MAX] for 15 s. The trip threshold varies depending on voltage rating of the drive as shown below.
Sub-trip Identification
Recommended actions:
Increase deceleration ramp (Pr 00.004)
Decrease the braking resistor value (staying above the minimum value)
Check nominal AC supply level
Check for supply disturbances which could cause the DC bus to rise
Check motor insulation using a insulation tester
OV.Fr Output frequency has exceeded the maximum frequency threshold
222 The OV.Fr trip indicates that the output frequency has exceeded 560 Hz for more than 100 ms.
P. dA t Power system configuration data error
220
The P. dA t trip indicates that there is an error in the configuration data stored in the power system.
Recommended actions:
Hardware fault – Contact the supplier of the drive
PAd Keypad has been removed when the drive is receiving the reference from the keypad
34
The PAd trip indicates that the drive is in keypad mode [Reference Selector (01.014) = 4 or 6] and the keypad has been
removed or disconnected from the drive.
Recommended actions:
Re-install keypad and reset
Change Reference Selector (01.014) to select the reference from another source
Trip Diagnosis
Voltage rating VM_DC_VOLTAGE[MAX] VM_DC_VOLTAGE_SET[MAX]
100 415 410
200 415 410
400 830 815
Source xx y zz
Control
system
00 0
01: Instantaneous trip when the DC bus voltage exceeds
VM_DC_VOLTAGE[MAX].
Control
system
00 0
02: Time delayed trip indicating that the DC bus voltage is above
VM_DC_VOLTAGE_SET[MAX].
Power
system
01 0
00: Instantaneous trip when the DC bus voltage exceeds
VM_DC_VOLTAGE[MAX].
Source xx y zz Description
Control
system
00 0 01 No data was obtained from the power board.
Control
system
00 0 02 There is no data table in node 1.
Control
system
00 0 03
The power system data table is bigger than the space available in
the control pod to store it.
Control
system
00 0 04 The size of the table given in the table is incorrect.
Control
system
00 0 05 Table CRC error.
Control
system
00 0 06
The version number of the generator software that produced the
table is too low.
Control
system
0 0 07 The power data table failed to be stored in the power board.
Power
system
01 0 00
The power data table used internally by the power module has an
error.
Power
system
01 0 01
The power data table that is uploaded to the control system on
power up has an error.
Power
system
01 0 02
The power data table used internally by the power module does
not match the hardware identification of the power module.