User guide
Safety
information
Product
information
Mechanical
installation
Electrical
installation
Getting
started
Basic
parameters
Running the
motor
Optimization NV Media Card
Advanced
parameters
Technical
data
Diagnostics
UL listing
information
Unidrive M100 User Guide 129
Issue Number: 1
Oht.P Power stage over temperature
22
This trip indicates that a power stage over-temperature has been detected. From the sub-trip ‘xxyzz’, the Thermistor
location is identified by ‘zz’.
Recommended actions:
• Check enclosure / drive fans are still functioning correctly
• Force the heatsink fans to run at maximum speed
• Check enclosure ventilation paths
• Check enclosure door filters
• Increase ventilation
• Reduce the drive switching frequency
• Reduce duty cycle
• Increase acceleration / deceleration rates
• Reduce motor load
• Check the derating tables and confirm the drive is correctly sized for the application.
• Use a drive with larger current / power rating
Oht.r Rectifier over temperature
102
The Oht.r trip indicates that a rectifier over-temperature has been detected. The thermistor location can be identified from
the sub-trip number.
Recommend actions:
• Check the motor and motor cable insulation with an insulation tester
• Fit an output line reactor or sinusoidal filter
• Force the heatsink fans to run at maximum speed by setting Pr 06.045 = 1
• Check enclosure / drive fans are still functioning correctly
• Check enclosure ventilation paths
• Check enclosure door filters
• Increase ventilation
• Increase acceleration / deceleration rates
• Reduce duty cycle
• Reduce motor load
OI.A1 Analog input 1 over-current
189 Current input on analog input 1 exceeds 24mA.
OI.AC Instantaneous output over current detected
3
The instantaneous drive output current has exceeded VM_DRIVE_CURRENT_MAX.
Recommended actions/checks:
• Increase acceleration/deceleration rate
• If seen during autotune reduce the voltage boost
• Check for short circuit on the output cabling
• Check integrity of the motor insulation using an insulation tester
• Is the motor cable length within limits for the frame size?
• Reduce the values in the current loop gain parameters
Trip Diagnosis
Source xx y zz Description
Power system 01 0 zz Thermistor location in the drive defined by zz
Source xx y zz Description
Power
system
Power module
number
Rectifier
number
zz Thermistor location defined by zz
Source xx y zz Description
Control
system
00 0 00
Instantaneous over-current trip when the measured a.c. current
exceeds VM_DRIVE_CURRENT[MAX].